9 Creating SNVTs TAC Xenta Server – Gateway, Technical Manual
76 (184) Schneider Electric Buildings AB, June 2011
04-00124-06-en
9.1.2 Connecting a Signal to an Output SNVT
An output SNVT created in the Xenta 913 is given its value by using a
connection object. For more information about connection objects, see
Section 10.2, “Connection Objects”, on page 87.
To connect a signal to an output SNVT
1 In the system pane, in the example, expand ACME_Gateway-
Engineering-Connection_Objects.
2 Right-click Connection_Objects, point to New, and then click
Folder.
3 Type the name. In the example “SNVTs”.
4 Right-click SNVTs, point to New, point to Object, and then click
Connection Object.
5 Type the name. In the example, “Tot_real_power”.
6 Expand the connection object.
7 In the system pane, from ACME_Gateway-Engineering-
PM710_Signals, drag Tot_real_power to the From signal in the
Tot_real_power connection object.
8 In the network pane, from IP Backbone-TAC_Xenta_913-SNVTs-
LonMarkObjects-Energy_Meter-NetworkVariables, drag
nvo_Tot_real_pow to the To signal in the Tot_real_power connec-
tion object.
9 In the system pane, click the Tot_real_power connection object.
10 In the properties pane, in the Send Option list, click Write on
change.
11 Generate and send the project to the Xenta 913.
Vedere la pagina 75
1 2 ... 71 72 73 74 75 76 77 78 79 80 81 ... 183 184

Commenti su questo manuale